KGL Operating Manual – UA 412 S
2019-01-14
/
110 122
V.-Satz POS: XXXXX
Input
Default
Min.A.Temp.
Minimum outside temperature for speed shift
0..50
35 °C
U.max.drehz.
Lower maximum speed for speed shift
71..100
80%
Max.A.Temp.
Maximum outside temperature for speed shift
0..60
42 °C
O.max.Drehz.
Upper maximum speed for speed shift
71..100
100%
VerdTempEIN
Lower limit value compressor end temperature
0..200
80 °C
VerdTempAUS
Upper limit value compressor end temperature
0..200
120 °C
Menu 6-3 Cooling
KÜHLUNG POS:
XXXXX
Input
Default
min. Laufzeit XX K
Minimum run time of the cooling
0..15
5 m
min. Standzeit XX m
Minimum switch-off time of the cooling
0..15
5 m
Dauerl.überw. XX m
Time for the forced interruption of the cooling during continuous operation
--, 0..
15
7 m
Notbetrieb XX m
If necessary sensors for the regulation fail, the solenoid valve is actuated with the opening degree in
[%]set here.
0..100
40%
Menu 6-4 - Language
SPRACHEPOS: XXXXX
Input
Default
Deutsch D
English GB
Français F
Menu 6-5 Alarm priorities
ALARMPRIOSPOS: XXXXX
Input
Default
Kühlstellenprio X
Priority of the alarms can be set
globally using the refrigeration point
priority (menu 6-1) (Y)
,
,
(Y,
N)
N
Priority: XX
Display of refrigeration point priority
(menu 6-1)
only displayed if Kühlstellenprio is set
to Y
The following priorities are only displayed if Kuhlstellenprio is set to N. The possible
entries for the priority of the alarms have the following meanings:
-=Event is ignored
0=Message (only entry in message list) 1=Alarm with priority 1 .. 99=Alarm with
priority 99
Low temp.
Lower alarm temperature limit value
undercut; priority is applicable for all
messages
low-temp. zone 1, low-temp.
zone 2
-, 0..
99
0
High temp
Upper alarm temperature limit value
exceeded; priority is applicable for all
messages
high-temp. zone 1, high-
temp. zone 2
-, 0..
99
1