KGL Operating Manual – UA 412 S
2019-01-14
/
46 122
Depending on the now set controller type, the respective functionalities are then displayed or hidden in the
menu of the controller. 8 controller types are available for the definition of the basic controller behaviour, see
chapter
Warning about dangerous electrical voltage!
Danger of electric shock! The DIP switch S3 may only be adjusted when disconnected from the
. The changes are not applied until the next time the controller is switched on.
power supply
DIP switch S3:
: Setting of the coding switches for the controller type SPIR290.
Example
The following controller types can be set using the DIP switch S3:
Controller type or master / slave mode
DIP switch S3 (switch positions of the coding switches 1 .. 8)
1
2
3
4
1)
5
6
7
8
Case controller
SPIR410
ON
OFF
OFF
ON/OFF
OFF
OFF
OFF
OFF
SPIR290
OFF
ON
OFF
ON/OFF
OFF
OFF
OFF
OFF
Due to the setting of the controller type, only a part of the functions and parameters of the case controller are
always available.
Operation with an unsupported DIP switch setting is not permitted. In the case of any setting of
coding switch combinations that are not present in the list, XXXXXX is automatically applied as
controller type and an alarm signal is created. In the event of change of the controller type, all
parameters are reset to their factory settings.
Master / Slave mode
1)
The Master / Slave mode is set using the coding switch of the DIP switch
:
4
S3