Installation and Startup of UA 410 D
42
Firmware V1.40 - Doku 2.1 06. April 2016
5.6
Basic configuration of the controller
The lock-down must previously be deactivated on the higher level controller (system centre / store computer or
operator terminal) so that configuration settings can be made on the controller.
1.
Deactivating the input lock-down
A. BT 300 operator interface
See chapter 7.2.1 for details.
B. System centre
Via Login symbol; see chapter 7.3.3.1 for details.
C. Store computer / operator terminal
Menu 9-3; see chapter 7.3.3.2 for details.
2.
Opening main menu of the controller
A. The main menu of the controller is shown directly in the operator interface.
B. In the system centre, select the required controller in
Menu 4-2
and then tap the
Remote Control
button to
display the main menu of the controller. See chapter 7.3.2.1 for details.
.
C. In the store computer and operating terminal, a selection list of all CAN bus components is displayed in Menu
5 Remote Control. Select the controller with the corresponding CAN bus address (Kn,nnn = 1..99) in the selec
tion list to be parametrised using the cursor or direct input and recall by tapping the
ENTER
button (
↵
) so that
the main menu of the controller is displayed. See chapter 7.3.2.2 for details.
3.
Basic configuration of the controller
- select refrigeration point (Menu 6-1)
The menus shown below only provide the overview; the display can be different for certain controller ty
pes. Details are described in the "Menu Structure" chapter.
6 Configuration - 1 Refriger.
Point
REFR. PT.
POS: XXXXX
Refr. Pt. Name:
XXXXXX
Check name of refrigeration point (can only be edited on Store Computer)
Item ID:
XXXXX
Check position of refrigeration point (can only be edited on Store Computer)
Priority:
X
Alarm priority 0 to 99 (See notes in Section Alarms)
Refr. Sys. No.:
X
No. of compressor pack supplying refrigeration point (1 to 9, important when seve
ral compressor packs are used)
Refr. Sys. Type
XXX
Zone of compressor pack supplying refrigeration point (Z1/Z2, with VS 3000 BS
only)
Temp. Zones
X
Division of refrigeration point in one zone mode or two zone mode
No. Sensors
XX
Number of sensors. The number of sensors connected is scanned on exiting the
parameter by pressing ENTER.
Содержание UA 410 D
Страница 8: ...vi Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 22: ...Application of UA 410 D 14 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 74: ...Pin and Terminal Assignments of UA 410 D 66 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 84: ...Operation of UA 410 D 76 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 132: ...Decommissioning and disposal 124 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 140: ...Specifications of UA 410 D 132 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 142: ...Order numbers and accessories of UA 410 D 134 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...