Function of UA 410 D
29
Firmware V1.40 - Doku 2.1 06. April 2016
S
NT coldrooms (normal-temperature coldrooms, UR 141 Zone 2 only)
The fan normally continues running during cooling and defrosting. When the parameter ”
Overrun Time
” is set
greater than 0 and ”
Fan Overrun
” is set other than “--”, the fan starts simultaneously with cooling and stops with
a delay when cooling is stopped. Stop delay is contingent on two conditions, both of which must be fulfilled:
‐ The set overrun time must have expired.
‐ Temperature on the evaporator sensor must be at or above the ”
Fan Overrun
” setpoint.
R1.1: Defrost
sensor
(Terminal
Z31/Z32)
R1.3: Defrost
sensor
(Terminal
Z81/Z82)
Valve 1:
Solenoid Valve 1 relay
(Terminal 25/26/28)
Valve 2:
Solenoid Valve 2 relay
(Terminal 35/36/38)
Fan 1:
Fan control relay
(Terminal 63/64)
Fan 2:
Fan control relay
(Terminal 73/74)