Specifications of UA 410 D
129
Firmware V1.40 - Doku 2.1 06. April 2016
11 Specifications of UA 410 D
11.1 Electrical data
Warning - hazardous electrical voltage!
Danger of electric shock!
Overvoltage category III (test voltage 4,0 kV)
/ pollution degree 2:
All device connections designed for use with 230 V AC supply voltage
must
be connected to the same phase conductor.
400 V AC between neighbouring connection terminals is
not
permitted!
Overvoltage category II (test voltage 2,5 kV)
/ pollution degree 2
or
Overvoltage category II (test voltage 2,5 kV) / pollution degree 1:
Different phase conductors may be used.
400 V AC between neighbouring connection terminals is
permitted!
UA 410 D AC
Power supply
230 V AC (+/- 10%), 50/60 Hz (+/- 3 Hz)
Rated power
11 VA
Leakage current over PE
Max. 1 mA
Rated surge voltage
2,5 kV (Overvoltage category II)
4,0 kV (Overvoltage category III)
Relay outputs
Relay
: 4 (N.O.) x 230 V AC, floating, min 10 mA
load type:
ohmic
max. 6 A
inductively
max. 3 A, cos
ϕ
= 0,4
3 (O.C.) x 230 V AC, floating, min 10 mA
load type:
ohmic
max. 6 A
inductively
max. 3 A, cos
ϕ
= 0,4
Transistor outputs
2 x 24 V DC pulldown, Switching transistor with internal current limiting to 50 mA for lighting
control
Digital inputs
4 x 230 V AC floating
Analogue inputs
10 temperature sensors, two-wire type
for sensor types L243 / K243, K277, 5K3A1 (No shielding is required on sensor leads when
installed exclusively inside the refrigerated display case and when external interference (for
example from parallel power wires) is not to be expected)
2 x 4..20 mA *
Analogue outputs*
2 x 0..10 V
short-circuit proof
Realtime clock
Battery-backed, Lithium cell (type CR 2450N, 3V lithium, shelf life 10 years)
Accuracy: typically 12 min/yr at 25
°
C
Содержание UA 410 D
Страница 8: ...vi Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 22: ...Application of UA 410 D 14 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 74: ...Pin and Terminal Assignments of UA 410 D 66 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 84: ...Operation of UA 410 D 76 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 132: ...Decommissioning and disposal 124 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 140: ...Specifications of UA 410 D 132 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 142: ...Order numbers and accessories of UA 410 D 134 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...