Installation and Startup of UA 410 D
43
Firmware V1.40 - Doku 2.1 06. April 2016
Danger of failure of alarm messaging in the event of problem!
Alarms can be suppressed by
setting Alarm Priority to 0. The case controller cannot receive the suction pressure value for control
functions
before
the Pack No. of the associated pack controller has been selected on the case con
troller.
Danger of damage to equipment and goods!
It must be ensured at all costs that the correct pack
number is selected, otherwise this can result in damage to the installation or goods.
Setting can be
checked under Refrigeration Point - 1 Actual Values - 1 Temperature Sensors. The value of t0 VS
corr. displayed is the actual value of t0 corrected by the offset for the pack controller specified in the
Pack No. field.
In stand alone operation via the local pressure transmitter, the pack number and the parameter
t0 VS corr.
only have meaning when the signal from the pressure transmitter is not available. In this
case the controller attempts to replace the missing signal with a pressure value measured at the
pack controller and transmitted via the CAN bus (if available).
With the installation or after a first start a sensor scan (menu 6-1)
must
be performed! The sensor
scan is the only possibility to define the sensors to be monitored, see chapter 4.1.1.
4.
Exiting configuration
:
Exit the menu
1 Refrigeration Point
by pressing the
ESC
button once and
choose menu
6 Configuration - 2 Controller
6 Configuration - 2 Controller
CONTROLLER
POS: XXXXX
1 Type and Version
Type, serial number and master-slave (ON/OFF)
2 Temp. Display
Matching of displayed temperature
3 Alarm Delay
Enter alarm time delay
4 230V Inputs
230 V inputs
5 Sensor Type
Select temperature sensor type (L243, K277 or 5K3A1)
5.
Select menu
6 Configuration - 3 Alarm Delay
6 Configuration - 2 Controller -
3 Alarm Delay
ALARMDELAY
POS: XXXXX
Sensor Fault
XX m
Alarm delay on sensor break
High/Low Temp.
XX m
Alarm delay on high or low temperature
No Defrost
XX h
Alarm is generated if defrosting does not take place within the set time
Selfholding
X
NO: Automatic reset of non-transient alarms
YES: Alarms must be reset manually
Press the
ESC
key one time to exit the menu.
Содержание UA 410 D
Страница 8: ...vi Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 22: ...Application of UA 410 D 14 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 74: ...Pin and Terminal Assignments of UA 410 D 66 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 84: ...Operation of UA 410 D 76 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 132: ...Decommissioning and disposal 124 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 140: ...Specifications of UA 410 D 132 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Страница 142: ...Order numbers and accessories of UA 410 D 134 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...