![Echelon LONWORKS PLT-22 Скачать руководство пользователя страница 55](http://html1.mh-extra.com/html/echelon/lonworks-plt-22/lonworks-plt-22_user-manual_3897121055.webp)
Table 4.5
100-240VAC, L-to-N, Isolated Coupling Circuit Component Values
Comp
Value
Specifications
Vendor / Part Number
C1
0.10µF
±10%,
≥
400VDC, metalized polyester
(1)
Matsushita Electric / ECQ-E4104KF
C2 0.82µF
±5%,
≥
50VDC, metalized polyester
Matsushita Electric / ECQ-V1H824JL
C3
≥
120µF
±20%, 16VDC, aluminum electrolytic,
≤
0.3
Ω
ESR @100kHz
Matsushita Electric / ECA-1CFQ121
C4 0.10µF
±5%,
≥
50VDC
AVX / R205C104JAA
D1 1A
Reverse
breakdown
≥
50V, surge current
≥
30A
for 8.3mS, reverse recovery
≤
200nS
1N4935
F1
6A
250VAC, slow blow
(2)
L3, L4
1.0mH
±10%, Imax
≥
30mA, RDC
≤
50
Ω
TAIYO YUDEN / LAL03NA102K
R1
1M
Ω
±5%, 1/4W, max working volt
≥
360VDC
(4)
R2
82
Ω
-L4RDC
(3)
±5%,
≥
1/16W
PROTECT 300VAC(470VDC)
300VAC(470VDC)
240VAC
For indoor branch circuits use 7mm varistor
For power entry use 14mm varistor
For outdoor use AC gas discharge tube
(5)
Matsushita Electric / ERZ-V07D471
Matsushita Electric / ERZ-V14D471
CPClare / AC240L
T1
See Appendix A
Table 4.6
100-120VAC, L-to-N, Isolated Coupling Circuit Component Values
Comp
Value
Specifications
Vendor / Part Number
C1 0.10µF
±10%,
≥
250VDC, metalized polyester
(1)
Matsushita Electric / ECQ-E2104KF
C2 0.82µF
±5%,
≥
50VDC, metalized polyester
Matsushita Electric / ECQ-V1H824JL
C3
≥
120µF
±20%, 16VDC, aluminum electrolytic,
≤
0.3
Ω
ESR @100kHz
Matsushita Electric / ECA-1CFQ121
C4 0.10µF
±5%,
≥
50VDC
AVX / SR205C104JAA
D1 1A
Reverse
breakdown
≥
50V, surge current
≥
30A
for 8.3mS, reverse recovery
≤
200nS
1N4935
F1 6A
125VAC, slow blow
(2)
L3, L4
1.0mH
±10%, Imax
≥
30mA, RDC
≤
50
Ω
TAIYO YUDEN / LAL03NA102K
R1 1M
Ω
±5%, 1/4W, max working volt
≥
200VDC
(4)
R2
82
Ω
-L4RDC
(3)
±5%,
≥
1/16W
PROTECT 150VAC(240VDC)
150VAC(240VDC)
120VAC
For indoor branch circuits use 7mm varistor
For power entry use 14mm varistor
For outdoor use AC gas discharge tube
(5)
Matsushita Electric / ERZ-V07D241
Matsushita Electric / ERZ-V14D241
CPClare / AC120L
T1
See Appendix A
(1)
In some applications an X2 safety rated capacitor may be required. Consult applicable safety standards.
(2)
In some applications a fuse may not be required. Consult applicable safety standards.
(3)
The value of R2 should be selected so that the series combination of the DC resistance of L4 and R1 is equal to 82
Ω
.
(4)
The working voltage rating of R1 may be achieved by using two 470k
Ω
resistors in series, each with a working
voltage rating of at least half of the value listed above.
(5)
Install the gas discharge tube on the line side of F1 (if a fuse is used).
L
ON
W
ORKS
PLT-22 Transceiver User’s Guide
4-21
Содержание LONWORKS PLT-22
Страница 6: ...iv Echelon...
Страница 14: ...1 8 Introduction...
Страница 67: ...LONWORKS PLT 22 Transceiver s User Guide 5 7 Figure 5 3 Capacitor Input Power Supply Schematic...
Страница 92: ...6 10 Design and Test for Electromagnetic Compatibility...
Страница 110: ...7 18 Communication Performance Verification...
Страница 114: ...8 4 References...
Страница 118: ...A 4 Appendix A...