Transmit Performance Verification
Use the following steps to verify that the transmit output impedance of the UUT is
low enough to adequately drive low impedance loads.
1
With a single PLCA-22 analyzer in idle mode (no packets being transmitted) and set
for C-band Internal and Line-to-Neutral coupling, connect the analyzer, the UUT,
the "5
Ω
load", and the Isolator as shown in figure 7.8 (if the UUT uses Line-to-Earth
coupling to a single power phase then the “7
Ω
load” should be used instead).
2
Verify that the UUT application program is not sending messages.
3
Press the service switch on the UUT.
4
Observe the primary signal strength LEDs on the PLCA-22 analyzer and check
which of the primary LEDs illuminate. If the UUT is configured for 3.5Vp-p
output (TXLVL, pin 21, on the PLT-22 transceiver is left open), all primary
signal strength LEDs up to, and including, the -6dB LED should flash for at least
6 out of 10 service pin messages from the UUT.
If the UUT is configured for 7Vp-p output (TXLVL, pin 21, on the PLT-22
transceiver is grounded), all primary LEDs up to, and including, the 0dB LED
should flash for at least 6 out of 10 service pin messages from the UUT.
Unit Under Test
(UUT)
service pin
PLCA-22
To power
mains
packet detect LED
ISOLATOR
2.4ž L-N Load
Isolated
Power
Line
5ž Load (7ž
load for sgl Ø L-E
UUT)
C-band
Figure 7.8
Transmit Performance Verification
7-10
Communication Performance Verification
Содержание LONWORKS PLT-22
Страница 6: ...iv Echelon...
Страница 14: ...1 8 Introduction...
Страница 67: ...LONWORKS PLT 22 Transceiver s User Guide 5 7 Figure 5 3 Capacitor Input Power Supply Schematic...
Страница 92: ...6 10 Design and Test for Electromagnetic Compatibility...
Страница 110: ...7 18 Communication Performance Verification...
Страница 114: ...8 4 References...
Страница 118: ...A 4 Appendix A...