Typ EP 501
Auxiliary functions
24.3.1. Description of the menu for the manual configuration of
X.TUNE
X.TUNE.CONFIG
Configuration.of.the.
X.TUNE
.
function
Specify which functions are to be executed when
X.TUNE
is running (automatic self-optimization).
M.TUNE.POS
Position.of.the.end.positions
- Specify whether the pneumatic actuator has
mechanical end positions.
- Manual specification of the end positions
If there are no mechanical end positions available,
these are not approached by the
X.TUNE
and must
be manually specified.
M.TUNE.PWM
Optimization.of.the.PWM.signals
Manual optimization of the PWM signals for control
of the aeration valves and bleed valves.
For optimization the valves must be aerated and
bled. A progress bar on the display indicates the
speed at which the valve is aerated or bled.
The setting is optimum when the progress bar
moves as slowly as possible.
M.TUNE.AIR
Determination.of.the.opening.
and.closing.times.of.the.actuator
Continuous determination of the opening and
closing times of the actuator.
24.3.1.1.
X.TUNE.CONFIG
– Configuration of the
X.TUNE
function
In this menu you can specify which functions are to be executed when the
X.TUNE
function is running
automatically.
Specifying.the.functions.in.
X.TUNE.CONFIG
Key
Action
Description
/
Select
X.TUNE.CONFIG
ENTER
Press
The functions for automatic self-parameterization by
X.TUNE
are
displayed.
/
Select required function
SELEC
Press
Activate the function by checking the box .
Select all required functions in succession using the arrow
keys / and
activate by checking the box .
EXIT
Press
Return to the
Manual.TUNE menu
.
Table 88:
X.TUNE.CONFIG; specifying the functions for automatic self-parameterization by X.TUNE