109
Typ EP 501
Auxiliary functions
24.2.14.2.
OUT BIN1 / OUT BIN2
- Configuring the binary outputs
The following description is valid for both binary outputs
OUT BIN 1
and
OUT BIN 2
, as the operation in the menu
is identical.
The binary outputs 1 and 2 can be used for one of the following outputs:
POS.Dev
Exceeding the permitted control deviation
POS.Lim-1/2
Current position with respect to a specified limit position (> or <)
Safepos
Actuator in safety position
ERR.SP/CMD
Sensor break (SP = process set-point value / CMD = set-point value position)
ERR.PV
Sensor break (process actual value).
Available.for.Type.EP.501.C.only.
Remote
Operating state (AUTOMATIC / MANUAL)
Tune.Status
Status
X.TUNE
(process optimization)
DIAG.State-1/2
Diagnosis output (option)
Overview.of.possible.outputs.and.associated.switching.signals:
Menu.option
Switching.signal Description
POS.Dev
0
Control deviation is within the set limit.
1
Control deviation is outside the set limit.
POS.Lim-1/2
0
Actual position is above the limit position.
1
Actual position is below the limit position.
Safepos
0
Actuator is not in the safety position.
1
Actuator is in the safety position.
ERR.SP/CMD
0
No sensor break available.
ERR.PV
1
Sensor break available.
Remote
0
Appliance is the AUTOMATIC operating state.
1
Appliance is the MANUAL operating state.
Tune.Status
0
The
X.TUNE
function is currently not running.
1
The
X.TUNE
function is currently running.
0/1 alternating
(10 s)
The
X.TUNE
function was stopped during execution by a fault.
DIAG.State-1/2
0
No diagnosis message available for the selected status signals.
1
Diagnosis message available for the selected status signals.
Table 48:
OUT BIN 1/2; Possible outputs and associated switching signals
Switching.signal
Switching.statuses
normally.open
normally.closed
0
0 V
24 V
1
24 V
0 V
Table 49:
OUT BIN 1/2; switching statuses