130
Typ EP 501
Auxiliary functions
24.2.22.
DIAGNOSE
– Menu for monitoring valves (option)
The optional function
DIAGNOSE
can be used to monitor the state of the valve. If there are deviations from the
set-point state, messages are output according to NE 107.
Example of the output of a diagnosis message:
Symbol for:
Diagnosis active
MENU CMD
POS MANU
POS
0.0
Status signal
Figure 74:
Example of a diagnosis message
24.2.22.1. Activation of the
DIAGNOSE
menu
To ensure that the
DIAGNOSE
menu can be set, it must first be activated in the main menu of the setting level (MAIN)
via
ADD.FUNCTION
. See Chapter “24.1. Activating and deactivating auxiliary functions”.
The active diagnosis is indicated on the display of the process level with a check mark symbol . See
“Figure 74”.
24.2.22.2. The
DIAGNOSE
main menu
The
DIAGNOSE
main menu consists of the following submenus.
EXIT
ENTER
29-1
D I A G N O S E
>>.D.MSG.<<
ADD.DIAGNOSE
RESET.HISTORY
CONFIG.MSG
D.MSG
(Diagnosis messages) list of all diagnosis messages.
CONFIG.MSG
Assignment of status signals for different diagnosis messages
according to NE 107 (NE = NAMUR recommendation).
ADD.DIAGNOSE
Activation of diagnosis functions by incorporation into the
DIAGNOSE
main menu.
RESET.HISTORY
Deletion of the history entries of all diagnosis functions.
The menu is only displayed if the
CLOCK
function has been
selected on the process level.
Table 66:
DIAGNOSE; main menu
The description can be found in Chapter “24.2.22.5. Description of the DIAGNOSE main menu”.