139
Typ EP 501
Auxiliary functions
Starting,.stopping.and.deleting.the.histograms
Key
Action
Description
/
Select
HISTOGRAM
(To do this, the
HISTOGRAM
function must be incorporated into
the
DIAGNOSE
main menu. See Chapter “24.2.22.4. Activation of
ENTER
Press
The empty matrix of the
POS-Class
submenu (dwell time density) is
displayed.
Starting.histograms:
START
*
Hold down
as long as countdown (5 ...) is
running
Both histograms (
POS class
and
DIR class
) are started.
/
Changing the display view
Selection options:
POS class
(Histogram for the dwell time density),
DIR class
(Histogram for the movement range),
SYSTEM DATA
(list of the characteristic values).
Stopping.histograms:
STOP
*
Hold down
as long as countdown (5 ...) is
running
The recording of both histograms (
POS class
and
DIR class
) is
stopped.
/
Changing the display view
Selection options:
POS class
(Histogram for the dwell time density),
DIR class
(Histogram for the movement range),
SYSTEM DATA
(list of the characteristic values).
Deleting.histograms:
CLEAR
*
Hold down
as long as countdown (5 ...) is
running
Both histograms (
POS class
and
DIR class
) are deleted.
Return.to.the.
DIAGNOSE
.main.menu:
/
Select
SYSTEM DATA
EXIT
Press
or
Return to the
DIAGNOSE
main menu.
*
The key functions
.
START
,
.
STOP
and
.
CLEAR
are available only in the display views of the histograms
POS
class
and
DIR class.
Table 74:
HISTOGRAM; starting, stopping and deleting histograms
english