Typ EP 501
Start-Up
21.
BASIC SETTING OF THE DEVICE
The following settings must be made for the basic setting of the device:
1.
INPUT
Selection of the input signal (see Chapter "21.1").
2.
X.TUNE
Automatic self-parameterization of the positioner (see Chapter "21.2")
Operating structure for the basic setting:
INPUT
X.TUNE
4-20 mA
CARACT
Select
parameters
0-20 mA
P.CONTROL
0-10 V
0-5 V
DIAGNOSE
X.TUNE.CONFIG
M.TUNE.POS
M.TUNE.PWM
M.TUNE.AIR
Press for approx. 3 s
Hold.down
as long as
countdown
(5 ...) is
running
X.TUNE
STARTED
TUNE #0
INIT
X.TUNE
READY
Process.level
(values are displayed)
Configuration
Select the input signal
Activating auxiliary functions
*
Manual.TUNE
, Manual parameterization
(not required for standard applications)
Automatic self-parameterization
MENU
Setting.level.
Main.menu.(MAIN)
EXIT
EXIT
ENTER
EXIT
ENTER
ENTER
SELEC
ENTER
SELEC
RUN
RUN
press.
briefly
EXIT
ADD.FUNCTION
EXIT
EXIT
* required only for start-up of the process controller (see Chapter
"22. Activation of the process controller")
Figure 22:
MAIN – main menu, operating structure in as-delivered state
english