83
Typ EP 501
Start-Up
23.5.2.1. Preparatory measures for execution of
P.TUNE
in the MANUAL
operating state
Moving.process.actual.value.
PV
.to.the.operating.point:
Key
Action
Description
Setting.on.the.process.level:
/
Select
PV
The process actual value
PV
is indicated on the display.
MANU
Press
Change to MANUAL operating state.The input screen for manually
opening and closing the valve is displayed.
Open valve
OPN
or
By opening or closing the control valve, move the process actual
value to the required operating point.
Close valve
CLS
As soon as the process actual value
PV
is constant, the
P.TUNE
function can be started.
Table 40:
P.TUNE; preparatory measure for running X.TUNE in the MANUAL operating state
23.5.2.2. Preparatory measure for execution of
P.TUNE
in the
AUTOMATIC operating state
By inputting a process set-point value
SP
, move the process actual value
PV
to the operating point.
Observe.the.internal.or.external.set-point.value.default.for.the.input.
(
P,CONTROL
→
SETUP
→
SP-INPUT
→
intern/extern)
:
For.intern.set-point.value.default:..
Input the process set-point value
SP
via the device keyboard
(see description below "Table 41" ).
For.extern.set-point.value.default:..
Input the process set-point value SP via the analog set-point value input.
Inputting.a.process.set-point.value:
Key
Action
Description
Setting.on.the.process.level:
/
Select
SP
The process set-point value is indicated on the display.
INPUT
Press
The input screen for inputting the process set-point value is displayed.
/
Input value
<–
Select decimal place
Increase value
The selected set-point value
SP
should be near the future operating
point.
OK
Press
Acknowledge input and return to the display of
SP.
Table 41:
P.TUNE; preparatory measure for running X.TUNE in the AUTOMATIC operating state
The process variable PV is changed according to the set-point value default based on the factory default PID parameters.
→
Before running the
P.TUNE
function, wait until the process actual value
PV
has reached a stable state.
To observe
PV,
it is recommended to select via the arrow keys / the graphical display
SP/PV(t)
.
To be able to select the display
SP/PV(t)
, it must be activated in the EXTRAS menu
(see Chapter "24.2.18. EXTRAS – Setting the display").
→
If
PV
oscillates continuously, the preset amplification factor of the process controller
KP
in the
menu
P.CONTROL
→
PID.PARAMETER
should be reduced.
→
As soon as the process actual value
PV
is constant, the
P.TUNE
function can be started.
english