Eaton xStorage 400 Installation and Operation Manual P-164001032—Rev 01
51
88..11..11
C
Coom
mm
muunniiccaattiioonn P
Prroottooccoollss
Table 7. Device Communication Protocol Detail
Device
Protocol
Predict Pulse
Communications traffic via LWM2M over TLS; Cellular Network, Private APN – MPLS2
Customer Portal
•
Remote access to operating parameters, HTTP over TLS
•
Customer API access, HTTP over TLS
Sample Parameters Available via Customer Portal:
•
System Status
•
Current Alarms
•
Battery State of Charge
•
Site Input Real Power
•
Eaton xStorage 400 Real Power
•
Site Load
•
Peak Monthly Demand
•
System Rating
•
Available Discharge Power
•
Current Discharge Power
88..22
D
Deem
maanndd R
Reessppoonnssee
Demand response programs offered by utility companies provide an opportunity to reduce financial burden by
shifting electricity usage during peak periods and limiting peak demand charges. The xStorage 400 can
discharge the Lithium Ion batteries as needed to decrease the load seen by the utility at a specific time. The
Eaton xStorage 400 EnergyAware Controller can be configured to provide demand response and peak shaving
functionality. Key parameters for the xStorage 400 demand response energy service are described below.
M
Maaxxiim
muum
m A
Accttiivvee S
Sttaattee--O
Off--C
Chhaarrggee ((S
SO
OC
C))
Highest operational state-of-charge that the system will utilize for the ancillary service and shall set an upper
boundary for ancillary services. The Maximum Active SOC must be set lower than the manufacturer Maximum
SOC and higher than the Target SOC with 1% or greater separation. The EAC will alarm when these conditions
are violated while a service is enabled. The participation in the Demand Response service will be halted while
the alarm is annunciated.
TTaarrggeett S
SO
OC
C
Nominal operational state-of-charge to which the battery is returned for the specific ancillary service. The
xStorage 400 charges and discharges the battery as required to obtain the Target SOC.
M
Miinniim
muum
m A
Accttiivvee S
Sttaattee--O
Off--C
Chhaarrggee ((S
SO
OC
C))
The lowest operational state-of-charge that the xStorage 400 system will utilize for the ancillary service.
Minimum Active SOC shall set a lower boundary for ancillary services. The Minimum Active SOC must be set
higher than the Minimum SOC and Critical Reserve SOC but lower than the Target SOC with 1% separation or
greater. The participation in the Demand Response service will be halted while the alarm is annunciated.
Содержание xStorage 400
Страница 6: ...vi Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Table of Contents...
Страница 8: ...viii Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 List of Figures...
Страница 10: ...x Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 List of Tables...
Страница 32: ...22 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Inspecting and Unpacking...
Страница 56: ...46 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Hydrogen Mitigation Procedure...
Страница 66: ...56 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Predict Pulse Dashboard...
Страница 86: ...76 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Warranty...
Страница 95: ...Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 85 Battery Safety Data Sheets...
Страница 96: ...P 16400103201 P 164001032 01...