Eaton xStorage 400 Installation and Operation Manual P-164001032—Rev 01
Figure 28. Eaton xStorage 400 Communication Network Diagram
EAI
#1 EV Ch
arger
U�lity
Site
Power
Meter
BESS
Power
Meter
COMMUNICATION NETWORK DIAGRAM
48VDC
SWITCHBOARD
(Customer Provided)
#2 EV Ch
arger
#3 EV Ch
arger
#4 EV Ch
arger
#5 EV Ch
arger
#6 EV Ch
arger
EAC
Wireless
Gateway
BESS
Ba�ery Energy
Storage System
C14
SUB
BESSB
Shunt Trip
Aux
GND
NEUT
SPD
I/O
Adapter
Aux
MODBUS
TCP/IP
12VDC
C12
Enclosure
Temp #1
AC #2
Fault
Forced Air
Fan #2
Enclosure
Temp #2
AC #1
Fault
Forced Air
Fan #1
AC #3
Fault
BESSD
Ba�ery
Rack #1
BMS
Ba�ery
Rack #2
BMS
CAN
Ba�ery
Rack #3
BMS
Ba�ery
Rack #4
BMS
CAN
CAN
CAN
System
BMS
MODBUS
RS-485
CAN
MODBUS
TCP/IP
Door
Open
Hydrogen
Detector
Enclosure
Vent #1
Enclosure
Vent #2
DC
Breaker #1
DC
Breaker #2
Remote
EPO
AC #4
Fault
BESS CMP
Control and Monitor Panel
Service
Port
C1
CT1
BESS
Control
Panel
TABLE C
CONTROL WIRING (SHEET 1 NOTES 10 AND 11)
CABLE #
CONNECTION
FROM
TO
NOMINAL
VOLTAGE
CABLE TYPE
CABLE PIN OUT
C1
SITE INPUT METER CT
SITE SWITCHGEAR CT
ɸA-X1, ɸA-X2, ɸB-X1,
ɸB-X2, ɸC-X1, ɸC-X2
CMP:
SBA1-1, SBA6-1, SBA3-1,
SBA4-1, SBA5-1, SBA2-1
480 VAC
8/C #12
C2
SITE INPUT METER PT
SITE SWITCHGEAR:
ɸA-V, ɸB-V, ɸC-V
CMP:
CBCMPB-1,2,3
480 VAC
4/C #12
C3
BESS METER CT
BESS DISCONNECT CT:
ɸA-X1, ɸA-X2, ɸB-X1,
ɸB-X2, ɸC-X1, ɸC-X2
CMP:
SBB1-1, SBB6-1, SBB3-1,
SBB4-1, SBB5-1, SBB2-1
480 VAC
8/C #12
C4
BESS METER PT
BESS DISONNECT:
ɸA-V, ɸB-V, ɸC-V
CMP:
CBCMPA-1,2,3
480 VAC
4/C #12
C5
SITE INPUT METER ETHERNET
IOM: EAC - P5
CMP: EPB
12 VDC
CAT6
C6
BESS METER ETHERNET
IOM: EAC - P4
CMP: EPA
12 VDC
CAT6
C7
EAC SERVICE ETHERNET
IOM: EAC - ENET1
CMP: EPS
12 VDC
CAT6
C8
EAI SERVICE PORT
IOM: IB-J12
CMP: DB9
5 VDC
DB9 SERIAL CABLE
1: NC, 2: TX, 3: RX,
4: DTR, 5: COM, 6: DSR,
7: NC, 8: NC, 9: NC
C9
POWER METER RS485
IOM: TBC-1,2,3
CMP: RSP-1,2,4
12 VDC
TWISTED SHIELDED PAIR
(MIN #22)
C10
EAI ON BUTTON
IOM: TB3-9, TB3-10
CMP: PBG-3, PBG-4
12 VDC
TWISTED PAIR #14
C11
EAI OFF BUTTON
IOM: TB3-7, TB3-8
CMP: PBR-3, PBR-4
12 VDC
TWISTED PAIR #14
C12
BESSD BREAKER AUX CONTACT
IOM: TB2-3, TB2-4
BESSD: AUX CONTACT
12 VDC
4/C #12
C13
BESSB BREAKER AUX CONTACT
BESSD: AUX CONTACT
BESSB: AUX CONTACT
12 VDC
4/C #12
C14
BESSB BREAKER SHUNT TRIP
IOM: TB2-1, TB2-2
BESSB: SHUNT TRIP
48 VDC
4/C #12
C5
MODBUS
TCP/IP
C6
C7
C8
C9
RS-485
MODBUS
TCP/IP
MODBUS
TCP/IP
RS-232
RS-485
RS-485
MODBUS
TCP/IP
MODBUS
TCP/IP
12VDC
C13
C10
12VDC
12VDC
C11
480VAC
C2
480VAC
PT1
CT2
PT2
C4
480VAC
C3
480VAC
Содержание xStorage 400
Страница 6: ...vi Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Table of Contents...
Страница 8: ...viii Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 List of Figures...
Страница 10: ...x Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 List of Tables...
Страница 32: ...22 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Inspecting and Unpacking...
Страница 56: ...46 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Hydrogen Mitigation Procedure...
Страница 66: ...56 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Predict Pulse Dashboard...
Страница 86: ...76 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Warranty...
Страница 95: ...Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 85 Battery Safety Data Sheets...
Страница 96: ...P 16400103201 P 164001032 01...