6 XC-152 as a SmartWire-DT coordinator
6.1 SmartWire-DT operator control and display elements
Compact PLC XC-152
05/17 MN050001ZU EN www.eaton.com
63
•
The power supply for the XC-152 and for SmartWire-DT must be
installed (1).
•
The SmartWire-DT network must be connected to the SmartWire-DT
interface (2).
▶
2. Switch on the power supply.
•
The SWD- master interface's POW LED must be lit up with a solid light.
•
The SmartWire-DT status LEDs of the connected SmartWire-DT mod-
ules must be flashing or showing a solid light.
•
There must be a PLC project in which the SWD master is configured
(project configuration).
•
The PLC runtime system must be installed on the XC-152.
SWD module scanning will start automatically when the device is powered.
Figure 23:
Commissioning SWD
▶
3. Press and hold down the "Config" button for at least 2 seconds (3).
•
The SWD LED on the SWD master interface must begin to flash orange
and the SWD status LEDs on the connected SWD modules must flash.
•
The SWD LED on the SWD master interface must start flashing green.
•
All SWD modules are addressed.
•
The SWD network's physical configuration must be stored in the XC-
152's retentive memory as a target configuration.
•
The SWD LED on the SWD master interface must light up with a solid
green light.
▶
4. Load the PLC project (XSoft-CODESYS) onto the XC-152.
•
If the project configuration is identical to the stored target configuration,
the Config LED lights up green and the data exchange of the input and
output data can start.
≧ 2 s
Config.
①
②
③
POW-LED
SWD-LED
Config.-LED
Содержание XC-152 Series
Страница 1: ...Manual XC 152 Compact Controller 05 17 MN050001ZU EN ...
Страница 4: ...2 ...
Страница 8: ...4 Compact PLC XC 152 05 17 MN050001ZU DE www eaton com ...
Страница 12: ...0 About this manual 0 4 Reading conventions 8 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 28: ...2 Safety regulations 2 3 Device specific hazards 24 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 42: ...3 Installation 3 6 Preparing the device for operation 38 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 74: ...8 Maintenance 8 4 Disposal 70 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 84: ...9 Technical data 9 8 Environmental conditions 80 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...