6 XC-152 as a SmartWire-DT coordinator
6.1 SmartWire-DT operator control and display elements
Compact PLC XC-152
05/17 MN050001ZU EN www.eaton.com
61
Conditions for Underwriters Laboratories Inc. (UL) listing
▶
The SmartWire-DT master interface's U
Aux
supply voltage must be
externally protected against overcurrent and short-circuits with the fol-
lowing:
•
Miniature circuit-breaker 24 VDC, rated operational current 2 A, trip-
ping characteristic Z
•
Or a 2 A fuse
Wiring
Figure 22:
WAGO plug connector (view from wiring side)
Observe the following when putting together the wiring for the plug connec-
tor:
→
The required plug connector is included with the device
plug connector
4 pole
PIN
signal
Configuration
1
+24 V DC POW
Supply voltage U
POW
+24 V DC
2
0 V POW
Supply voltage U
POW
0 V
3
+24 V DC AUX
Supply voltage U
AUX
+24 V DC
4
0 V AUX
Supply voltage U
AUX
+0 V
Plug connector wiring
Description/Value
Terminal type:
spring-cage terminal
Cross section
0.2 - 1.5 mm
2
(connectable conductor, solid)
AWG24 - AWG16
Strip length
6 -7 mm
0 V AUX
+24 VDC AUX
0 V POW
+24 VDC POW
0 V
24 V DC
F2
POW
F1 ≦ 3 A
UL: F2 ≦ 2 A
IEC: F2 ≦ 3 A
F1
AUX
U
e
= 24 V DC
(20.4 - 28.8 V DC)
I
e
= 700 mA
Содержание XC-152 Series
Страница 1: ...Manual XC 152 Compact Controller 05 17 MN050001ZU EN ...
Страница 4: ...2 ...
Страница 8: ...4 Compact PLC XC 152 05 17 MN050001ZU DE www eaton com ...
Страница 12: ...0 About this manual 0 4 Reading conventions 8 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 28: ...2 Safety regulations 2 3 Device specific hazards 24 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 42: ...3 Installation 3 6 Preparing the device for operation 38 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 74: ...8 Maintenance 8 4 Disposal 70 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 84: ...9 Technical data 9 8 Environmental conditions 80 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...