7 Malfunctions
66
Compact PLC XC-152
05/17 MN050001ZU EN www.eaton.com
→
Whenever there is a red LED, there is an abnormal operating state.
LED status
Fault and
possible cause
Remedy
RUN/STOP
SF
COM
While the device is starting (booting)
Off
Off
Off
Power supply interface does
not have any power.
Check the input wiring.
Orange
Orange
Orange
Hardware fault
UPD/RUN jumper is set incor-
rectly.
Set the UPD/RUN jumper to the
RUN position.
If the UPD/RUN jumper is set to the
RUN position, send in the device for
repairs.
Orange
What-
ever
Orange
flashing
There is no SD card inside the
SD slot.
Insert an SD card with the operating
system into the SD slot.
You can boot the device with the
internal operating system by
pressing the CTRL button.
Orange
What-
ever
Red
flashing
The operating system on the
SD card is obsolete or was
not found.
Copy a new operating system onto
the SD card.
You can boot the device with the
internal operating system by
pressing the CTRL button.
Orange
Orange
Off
Boot error. Occurs if:
An invalid operating system
is stored in InternalStorage.
Store a valid operating system in
InternalStorage.
The internal operating system
was started due to the CTRL
button being pressed (oper-
ating system from Inter-
nalStorage).
Store a valid operating system on
the SD card.
During operation
Off
Off
Off
No power supply voltage.
Check the input wiring.
Orange
Orange
Orange
UPD/RUN jumper set incor-
rectly.
Set the UPD/RUN jumper to the
RUN position.
Hardware fault
If the UPD/RUN jumper is set to the
RUN position, send in the device for
repairs.
Orange/green
flashing
No PLC program present.
Save PLC Program on device.
Orange
Re
PLC system error
Check the PLC program
Содержание XC-152 Series
Страница 1: ...Manual XC 152 Compact Controller 05 17 MN050001ZU EN ...
Страница 4: ...2 ...
Страница 8: ...4 Compact PLC XC 152 05 17 MN050001ZU DE www eaton com ...
Страница 12: ...0 About this manual 0 4 Reading conventions 8 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 28: ...2 Safety regulations 2 3 Device specific hazards 24 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 42: ...3 Installation 3 6 Preparing the device for operation 38 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 74: ...8 Maintenance 8 4 Disposal 70 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 84: ...9 Technical data 9 8 Environmental conditions 80 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...