6 XC-152 as a SmartWire-DT coordinator
6.1 SmartWire-DT operator control and display elements
60
Compact PLC XC-152
05/17 MN050001ZU EN www.eaton.com
6.1.1 POW/AUX SWD power supply
This connection ensures that the power required for the SmartWire-DT net-
work will be supplied.
Characteristics: WAGO connector, 4-pole, not galvanically isolated
The following power supplies are required for a SmartWire-DT network:
•
POW supply voltage:
The device supply voltage for the electronics in the downstream SWD-
modules (15 VDC) is generated using the 24 VDC supply voltage applied
at the POW terminal.
•
AUX supply voltage:
If there are any contactors or motor starters in the SWD- topology, a 24
VDC AUX voltage must be additionally supplied as a control voltage for
the contactor coils.
.
Operator control and display
elements for SmartWire-DT
Description
a
bc
d
POW/AUX
SWD power supply
Power supply for the SmartWire-DT network
a
+24 V DC POW,
b
0 V DC POW,
c
+24 V DC AUX,
d
0 V DC AUX
e
POW-LED
Lights up when the SmartWire-DT network is powered.
f
SWD-LED
Indicates whether the physical configuration of the SmartWire-DT
network matches the target configuration stored in the device.
The configurations will be compared with each other every time the
power is switched on.
g
Config-LED
Indicates whether the SWD master project configuration defined in the
PLC matches the SmartWire-DT network target configuration stored in
the device. The configurations will be compared with each other every
time the power is switched on.
h
SWD Interface
SmartWire-DT ribbon cable connection
i
Config
configuration button
Used to configure the SmartWire-DT network.
→
If contactors and/or motor starters with a total current draw > 3
A (DIN VDE 0641, Part 11 and IEC/EN 60898) or > 2 A (UL 508
and CSA-22.2, No. 14) are connected, an EU5C-SWD-PF1 or
EU5C-SWD-PF2 power feeder module needs to be used.
→
If SmartWire-DT modules with a total current draw > 0.7 A are
connected, an EU5C-SWD-PF2-1 power feeder module needs
to be used.
Содержание XC-152 Series
Страница 1: ...Manual XC 152 Compact Controller 05 17 MN050001ZU EN ...
Страница 4: ...2 ...
Страница 8: ...4 Compact PLC XC 152 05 17 MN050001ZU DE www eaton com ...
Страница 12: ...0 About this manual 0 4 Reading conventions 8 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 28: ...2 Safety regulations 2 3 Device specific hazards 24 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 42: ...3 Installation 3 6 Preparing the device for operation 38 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 74: ...8 Maintenance 8 4 Disposal 70 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 84: ...9 Technical data 9 8 Environmental conditions 80 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...