3 Installation
3.6 Preparing the device for operation
36
Compact PLC XC-152
05/17 MN050001ZU EN www.eaton.com
3.6.1 Power supply 24 V DC
The device has an internal fuse and protection against polarity reversal.
The power supply for the device is not galvanically isolated.
The device requires a rated operating voltage of 24 VDC.
The functional earth is connected to the connector cover only, and not to 0 V.
The housing is made of plastic and is isolated.
•
SELV (safety extra low voltage):
circuit in which no dangerous voltage occurs even in the event of a sin-
gle fault.
Connector MSTB 2.5/3-ST-5.08 is included as standard.
Cable and terminal specifications
CAUTION
The voltage being applied must meet the requirements for
safety extra-low voltages (SELV) set forth in IEC 60950.
Pay attention to the polarity!
→
Section "9.3 Power supply”, page 73
Terminal type:
Screw terminal plug-in
Cross section
min. 0.75 mm
2
/ max. 2.5 mm
2
(drain wire or conductor)
min. AWG18 / max. AWG12
Strip length
7 mm
Max. tightening torque
0.6…0.8 Nm / 5…7 Lb. In.
Содержание XC-152 Series
Страница 1: ...Manual XC 152 Compact Controller 05 17 MN050001ZU EN ...
Страница 4: ...2 ...
Страница 8: ...4 Compact PLC XC 152 05 17 MN050001ZU DE www eaton com ...
Страница 12: ...0 About this manual 0 4 Reading conventions 8 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 28: ...2 Safety regulations 2 3 Device specific hazards 24 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 42: ...3 Installation 3 6 Preparing the device for operation 38 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 74: ...8 Maintenance 8 4 Disposal 70 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 84: ...9 Technical data 9 8 Environmental conditions 80 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...