3 Installation
3.3 Communication cables
Compact PLC XC-152
05/17 MN050001ZU EN www.eaton.com
29
3.3.1 Preparing the cables with the SUB-D plug
The design of the wiring is an essential factor for reliable operation and elec-
tromagnetic compatibility (EMC).
3.3.1.1 Wiring requirements
•
The cables must be screened.
•
The cable screen must consist of a copper braid.
•
This cable screen must be terminated to the connector shell with a low-
impedance bond across a large area.
3.3.1.2 Connecting the cable screen
Figure 4:
Connecting the cable screen
▶
1. Insulate the cable end so that approx. 3 cm of screen braid is exposed
①
.
▶
2. Fold back the screen braid over the cable sheath
②
.
▶
3. Attach heat-shrink tubing approx. 3 cm in length over the folded screen
braid or use a rubber grommet.
•
5…8 mm of the screen braid must be exposed at the cable end.
•
The folded screen braid end must be covered by the heat-shrink tub-
ing or the rubber grommet
③
.
▶
4. Fit the SUB-D plug to the cable end:
•
The exposed metal screen braid must be clamped to the connector
casing with the cable clamp.
NOTICE
The EMC values stated in the technical data (immunity and
emission) can only be guaranteed by observing this prescribed
preparation!
30 mm
5…8 mm
1
2
3
Содержание XC-152 Series
Страница 1: ...Manual XC 152 Compact Controller 05 17 MN050001ZU EN ...
Страница 4: ...2 ...
Страница 8: ...4 Compact PLC XC 152 05 17 MN050001ZU DE www eaton com ...
Страница 12: ...0 About this manual 0 4 Reading conventions 8 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 28: ...2 Safety regulations 2 3 Device specific hazards 24 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 42: ...3 Installation 3 6 Preparing the device for operation 38 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 74: ...8 Maintenance 8 4 Disposal 70 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...
Страница 84: ...9 Technical data 9 8 Environmental conditions 80 Compact PLC XC 152 05 17 MN050001ZU EN www eaton com ...