Installation
64
02/11 MN05006002Z-EN
Installation of the surface mounting enclosure
The circuit-board in the surface mounting enclosure is
connected to the SmartWire-DT network with the Smart-
Wire-DT round cable.
The SmartWire-DT round cable can be connected directly
with V-M20 × 1.5 mm (metric cable gland with integrated
strain relief) or plugged in (
Wire-DT round cable“, page 65).
8-pole enclosure bushings with a screw fixing
M20 x 1.5 mm as plug/socket versions are used for the plug-
in version (
“Plug-in connection of the SmartWire-DT
Connection on the PCB is performed via eight numbered and
colour-coded spring-cage terminals. This applies to the
incoming SmartWire-DT cable on the PCB side marked IN
and to the outgoing SmartWire-DT cable on the OUT side.
The SmartWire-DT round cable and SmartWire-DT enclosure
bushings have the same wire colours.
Connection to the printed circuit board
Figure 17:
Printed circuit board
X
Place the PCB in the mounting of the surface mounting
enclosure so that the terminal strip is lying with the
marking IN on the side of the incoming SmartWire-DT
round cable.
IN
OUT
OFF
ON
www.comoso.com