Switching on when there are
configuration changes
103
02/11 MN05006002Z-EN
In the case of a changed actual configuration the continued
behavior of the operator is governed by whether the change
has been created deliberately or by an unwanted influencing
of the SmartWire-DT topology. In any case the following is
valid:
X
Prior to reconfiguration interrupt the connection to the
field bus master by pulling out the field bus plug.
Switching on in the case of a deliberately changed
actual configuration
In this case the changed actual configuration must be saved
as a new target configuration.
X
Press the
“Config.”
pushbutton actuator for at least
2 seconds.
Please refer to the table “LED indication after creating a new
target configuration”.
X
Change the project configuration for the field bus master
in the configuration software for the PLC in accordance
with the changed actual configuration.
X
Reconnect to the field bus master.
The SmartWire-DT gateway is then in the SmartWire-DT
mode “Normal” and is ready for data interchange.
h
Caution!
First of all check whether your actual configuration has
been changed unintentionally, e.g. by unclamping an
external device plug.
In this case the changed actual configuration must not be
saved as a new target configuration because an Smart-
Wire-DT slave that can no longer be found would thereby
be removed permanently from the target configuration.