Connecting the SmartWire-DT
connection cable
93
02/11 MN05006002Z-EN
X
Connect the 8 conductors of the round cable in accor-
dance with their colour to the spring-cage terminals of the
same colour.
X
Insert the ribbon cable into the adapter socket.
Using network termination
The SmartWire-DT network must be terminated at the begin-
ning and at the end with a network termination.
Network termination for an installed ribbon cable
If the SmartWire-DT network ends with a ribbon cable, a
ribbon cable plug must be connected there.
X
Connect the ribbon cable to the SmartWire-DT network
termination (part no. SWD4-RC8-10).
i
Caution!
Ensure the secure seating of the round cable and safe
operation by using cable binders for strain relief.
i
Warning!
For correct polarity the black conductor of the ribbon cable
must be inserted into the adapter so that it is lying next to
the line shown in black with the desig15 V.
h
To also supply the 24 V DC contactor control voltage
when changing from ribbon cable to round cable, use the
adapter for the switch cabinet bushing (