SmartWire-DT network
27
02/11 MN05006002Z-EN
Round conductor
Round conductors are used outside the control panel and are
suitable for bridging larger distances (
SmartWire-DT connection cable“, page 80).
The conductors for the supply of the device supply voltage
and contactor control voltage have a cross-section of
0.5 mm
2
, the other conductors 0.22 mm
2
each. See below
for the configuration of the round cable conductors.
Table 6:
Configuration of SmartWire-DT round cable
Core
Cross-
section
[mm
2
]
Conduct
or colour
Meaning
1
0.5
brown
+15 V DC
Device supply voltage
2
0.22
gray
SEL
Select cable for automatic addressing of
the SmartWire-DT slaves
3
0.22
pink
GND
for device supply voltage and data cable
4
0.22
red
Data A
Data cable B
5
0.22
blue
Data B
Data cable A
6
0.5
white
GND
for device supply voltage and data
7
0.5
yellow
Common
Contactor control voltage
8
0.5
green
+24 V DC
Contactor control voltage
www.comoso.com