System Operation
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
43
► To configure a Smart Alarm Disconnect
1
In DCTools/Web go to:
Alarms
>
Smart Alarms
. Configure a
Smart Alarm
as described on
2
Note the
SA Number
(first column of the
Smart Alarm States
table).
3
Go to:
Control Processes
>
LVD
.
4
For the required LVD control channel:
Set
Smart Alarm Index
to the
SA Number
(first column of the
Smart Alarm States
table).
Set
Smart Alarm based Disconnect
to
Enabled
.
The LVD control channel will disconnect its contactor(s) if the
Smart Alarm
becomes active.
Except, if
Chained to Previous
is enabled then the preceding LVD control channel must be
disconnected first.
Alarms
An SC200 supplied with a standard configuration file (see details on page
) has a standard set
of alarms configured and enabled. This will be sufficient for standard dc power system
operation.
For specific alarm arrangements all SC200 alarms can be individually enabled or disabled and
are configurable.
Types of Alarms
The SC200 provides five types of alarms:
Alarm type
Description
Configuration
System alarms
Generated by the operating values of dc power
system (voltages, currents, temperatures, and
so on) and the operation of power system
modules (rectifiers, circuit breakers, fuses, and
so on). The SC200 system alarms are listed in
Alarm Descriptions on page
See details on page
Analog Input
(AI) High alarms
Activated when the input value of an AI is
above the alarm threshold.
See details on page
Analog Input
(AI) Low alarms
Activated when the input value of an AI is
below the alarm threshold.
See details on page
Digital Input (DI)
alarms
Activated when a DI is in its active state.
See details on page
Smart Alarms
Software simulation of logic gates to allow the
logical combination of other alarms, time
schedules and/or system values.
See details on page
Содержание SC200
Страница 4: ......
Страница 8: ......
Страница 28: ...SC200 Handbook 20 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 88: ...SC200 Handbook 80 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 116: ...SC200 Handbook 108 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 120: ...SC200 Handbook 112 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 130: ...SC200 Handbook 122 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 134: ...SC200 Handbook 126 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...