SC200 Handbook
70
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
Alternative Energy Input Metering
The SC200 can meter currents supplied to the DC bus from alternative energy sources such as
solar or wind. This means that it can calculate currents to and from the DC bus correctly, even
when both rectifiers and alternative energy sources are providing power.
► To set up alternative energy input metering
For each alternative energy source, connect a current sensor from the energy source to an
analog input.
In DCTools/Web go to:
Analog Inputs
.
Configure the selected Analog Inputs and set
Function
to
Alternative Energy Source Current
.
The alternative energy source current is calculated as the sum of the currents of all analog
inputs configured as
Alternative Energy Source Current
.
Smart Alarms based on System Value Sources can be used to configure alarms based on the
Alternative Energy Source Current
.
See Smart Alarms on page
for details of how to set Smart Alarms.
The System Summary displayed in DCTools and the System Schematic shown in the SC200 web
page displays the source current values (rectifiers and alternative energy sources) and load current
values (load and batteries). If one of these values is not available, it is calculated from the other
system current values.
Input/Output (I/O)
The following section describes the I/O functions available with a single IOBGP I/O board.
Also see I/O Board Mapping on page
Optional SiteSure-3G input/output (I/O) modules or additional IOBGP I/O boards can be
connected to the SC200 to provide additional I/O to monitor and control external devices. For
details refer to the SiteSure-3G Installation Guide (see Related Information on page
Identify an I/O Board
Input/Output (I/O) boards and SiteSure-3G modules are referenced by their serial numbers.
► To identify a particular I/O board or SiteSure-3G module
Either:
On SC200 keypad go to:
Settings
>
IOBs
and select a module or board. Press
Enter
.
The I/O board details screen appears. Use
to scroll to other I/O boards.
The Power-on LED on the selected I/O board or SiteSure-3G module will flash for 60
seconds (or press
Esc
to stop).
Or:
In DCTools/Web go to:
Configuration
>
RXP
>
RXP Devices
.
DCTools: select
Identify Device
or Web: click on
Start Identifying
.
The Power-on LED on the selected I/O board or SiteSure-3G module will flash for 60
seconds.
Содержание SC200
Страница 4: ......
Страница 8: ......
Страница 28: ...SC200 Handbook 20 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 88: ...SC200 Handbook 80 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 116: ...SC200 Handbook 108 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 120: ...SC200 Handbook 112 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 130: ...SC200 Handbook 122 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 134: ...SC200 Handbook 126 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...