SC200 Handbook
52
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
► To configure the Source(s) for a Smart Alarm
Configure the following parameters for the source(s) for each
Smart Alarm
.
Every Smart Alarm must have at least one Source assigned to it.
Alarm Sources
Parameter
Setting
SA Num
Type the number (from the
Smart Alarm States
table) of the
Smart Alarm
for
which this source is an input.
Status
Set to
Enabled
.
Logic
Set to either:
EQUAL
- the Alarm Source will become active when the source
alarm is Triggered or Active.
NOT
- the Alarm Source will become active when the source alarm
is Inactive.
Trigger When
Source Is
Set to either:
Triggered
- the Alarm Source will become active immediately
when the conditions for this alarm become true (or false when
Logic
is set to NOT). The alarm does not have to be
Enabled
.
Do not use Triggered when Type is set to Smart Alarm.
Active
- the Alarm Source will become active when the alarm
becomes active (or inactive when
Logic
is set to NOT), after the
alarm recognition time, and only if the alarm is
Enabled
.
Type
Set to the appropriate source type:
System Alarm
,
Analog Input High
,
Analog
Input Low
,
DI
,
Smart Alarm
.
Index
Identify the alarm:
Source Type
=
System Alarm
:
DCTools - type the alarm number from the
Alarm States
table.
Web - select the name of the system alarm from the list.
Source Type
=
AI High/AI Low
- type the alarm number from the
Analog Input High Alarms
or the
Analog Input Low Alarms
table.
Source Type
=
DI
- type the alarm number from the
Digital Input
Alarms
table.
Source Type
=
Smart Alarm
- type the alarm number from the
Smart
Alarm States
table.
Содержание SC200
Страница 4: ......
Страница 8: ......
Страница 28: ...SC200 Handbook 20 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 88: ...SC200 Handbook 80 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 116: ...SC200 Handbook 108 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 120: ...SC200 Handbook 112 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 130: ...SC200 Handbook 122 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 134: ...SC200 Handbook 126 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...