SC200 Handbook
60
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
Configuration
It will take at least 10 hours to characterize a battery.
When a battery is characterized it is discharged. The bus voltage will gradually
reduce to the battery end voltage. Ensure that this will not affect the operation of
any equipment connected to the dc power system.
Use the following procedure to configure
Battery Time Remaining
for the first time, or if a
previously characterized battery is changed.
Battery Characterization is not necessary if a previously saved battery characterization data file is
available. Refer to Characterization Data Management on page
. Only use characterization data
for an identical type and size of battery.
► To configure
Battery Time Remaining
1
Check that all battery strings are connected and all LVD contactors (if any) are connected.
During a battery characterization, LVD contactor disconnection is inhibited. If any LVD
contactor is configured to connect during a battery discharge then set it to Manual Connect to
prevent operation during the battery characterization.
2
Check that all battery strings are fully charged.
When a battery is fully charged, the Battery Charge State will be Float and Ah Discharged
will be zero. See Batteries on page
3
Check that all battery parameters are set to the correct values. See Batteries Configuration
on page
4
Check that the load current is at least 2% of the C10 capacity of the batteries (
Battery
Capacity
) and 150% of the
Battery State Threshold
. See Batteries Configuration on page
If the load current is less than 10% of the C10 capacity of the batteries, then Battery
Characterization will take longer than 10 hours.
5
Either, in DCTools/Web go to
Batteries
>
Battery Time Remaining,
or use the SC200 keypad
to go to
Battery
. Set
End Voltage
to the voltage per cell when the battery is regarded as fully
discharged.
In general set the end voltage to the same value as for the LVD Disconnect Voltage (see LVD
Configuration on page
). End Voltage must be at least 0.02V/Cell above the Minimum
System Voltage (per cell). The Minimum System Voltage is viewable in DCTools/Web at
Control Processes. It is not configurable.
6
Enable
Battery Current Limit
Содержание SC200
Страница 4: ......
Страница 8: ......
Страница 28: ...SC200 Handbook 20 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 88: ...SC200 Handbook 80 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 116: ...SC200 Handbook 108 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 120: ...SC200 Handbook 112 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 130: ...SC200 Handbook 122 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 134: ...SC200 Handbook 126 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...