Battery Mid-point Monitoring (MPM)
Battery Mid-point Monitoring provides a cost-effective method for the early detection of
internal battery faults. The voltages of the two halves of a battery string are measured and the
system controller generates an alarm signal if a voltage imbalance is detected.
A voltage imbalance is an indication that one or more cells has an internal fault. Further
investigation can then isolate the faulty cell(s) and action can be taken to correct the problem
and prevent a total battery failure.
To connect Battery Mid-point Monitoring see details in the dc power system Installation and
Operation Guide. If a
String Fail
alarm is generated see Troubleshooting on page
To ensure reliable operation Mid-point Monitoring operates only when the battery is in float
charge and after a configurable lockout period since the last battery discharge, Fast Charge,
Equalize or Battery Test.
► To enable
Battery Mid-point Monitoring (MPM)
If any of the mid-point monitoring analog inputs are used for Reverse Battery Detection (see
details on page
) then they are not available for MPM.
1
Connect the mid-point monitoring sense wires to the batteries. Refer to the dc power
system Installation and Operation Guide.
There are four mid-point monitoring analog inputs on an IOBGP input/output board (for four
battery strings). Up to 20 additional battery strings can be monitored if additional IOBGP
input/output boards are connected. Refer to the dc power system Installation and Operation
Guide for details on how to connect additional IOBGP input/output boards to the SC200.
2
In DCTools/Web go to
Batteries
.
3
Set
Cells Per String
to the number of 2V cells per string (for example: 24 for 48V nominal
system).
4
Expand the
Mid-point Monitoring
table.
5
Set
MPM Enable
to
Enabled
and check the configuration settings (see details on page
6
Go to
Analog Inputs
and
Enable
the mid-point monitoring analog inputs (one per battery
string) as required.
Battery strings 1-4 will be connected to IOB Number 1, IOB AI Numbers 2-5. Battery strings
5-8 will be connected to IOB Number 2, IOB AI Numbers 2-5. And so on, as required up to
string 24.
7
Go to
Alarms
>
Alarm States
. Enable and configure the
String Fail
alarm. See System Alarm
Configuration on page
► To clear a
String Fail
alarm
1
In DCTools/Web go to
Batteries
>
Mid-point Battery Monitoring
(expand the
table).
2
Click on
Clear String Fail
.
Содержание SC200
Страница 4: ......
Страница 8: ......
Страница 28: ...SC200 Handbook 20 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 88: ...SC200 Handbook 80 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 116: ...SC200 Handbook 108 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 120: ...SC200 Handbook 112 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 130: ...SC200 Handbook 122 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 134: ...SC200 Handbook 126 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...