![Eaton SC200 Скачать руководство пользователя страница 77](http://html1.mh-extra.com/html/eaton/sc200/sc200_operation-handbook_3771908077.webp)
System Operation
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
69
Fuel Management
The SC200 can monitor the use of fuel by a standby generator.
► To set up fuel management
Connect a fuel level sensor to an analog input.
In DCTools/Web go to:
Analog Inputs
.
Configure the selected Analog Input and set
Function
to
Fuel Level
.
Go to:
Control Processes
>
Generator Control
and set
Fuel Tank Volume
.
The following information is available about fuel usage.
Parameter
Description
Where to find:
Fuel Level
The volume of fuel in the generator's fuel tank.
SC200: Control Processes >
Generator Control
DCTools/Web: Control
Processes > Generator
Control
Generator Refuel
Date
The time and date the generator was last
refueled.
Generator Refuel
Volume
The amount of fuel added to the generator's fuel
tank during the last refuel.
Generator Backup
Time
The estimated time for which the generator
could continuously run based on the current fuel
level and historical fuel consumption.
Tank Empty Date
The best current estimate of the date the fuel
tank will run dry if the current characteristics of
generator usage and fuel consumption do not
change. This is useful for installations that run
the generator regularly and with a reasonably
constant duty cycle.
The time remaining estimates will not be accurate if the generator has been replaced or if the
typical usage pattern has changed. If this happens, the fuel consumption history can be cleared
manually.
Clearing the fuel consumption history will cause the time remaining estimates to be inaccurate or
not available until enough information about the new generator has been collected.
► To clear the fuel consumption history
In DCTools/Web go to:
Control Processes
>
Generator Control > Clear Fuel Consumption
History
.
Smart Alarms based on System Value Sources can be used to configure alarms based on:
Fuel Level.
Generator Backup Time.
Fuel Remaining Time (this is the estimated
Tank Empty Date
).
for details of how to set Smart Alarms.
Содержание SC200
Страница 4: ......
Страница 8: ......
Страница 28: ...SC200 Handbook 20 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 88: ...SC200 Handbook 80 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 116: ...SC200 Handbook 108 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 120: ...SC200 Handbook 112 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 130: ...SC200 Handbook 122 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 134: ...SC200 Handbook 126 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...