System Operation
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
59
Configuration
Set the following parameters.
Parameter
Description
Where to find:
String Fail alarm
parameters
See System Alarm Configuration on page
DCTools/Web: Alarms >
Alarm States
MPM Enable
Enable/disable Mid-point Monitoring.
SC200: Battery > MPM >
Settings
DCTools/Web: Batteries >
Mid-point Monitoring
MPM Lockout
Period*
Time from when MPM is able to start until the
start of the
MPM Convergence Period
.
MPM Convergence
Period*
Time from the end of the
MPM Lockout Period
until
MPM State
is
Stable
. During this period the
Current MPM Threshold
is calculated using linear
interpolation between
Start Threshold
and
Stable
Threshold
and the
MPM State
is defined as
Converging
. After this period the
MPM State
is
defined as
Stable
and the
MPM Stable Threshold
applies.
String Fail
Recognition Period
If the mid-point
Imbalance
percent of a battery
string exceeds the
MPM Threshold
for this period
of time the
String State
is set to
Fail
and the
String
Fail
alarm is activated.
MPM Start
Threshold*
Mid-point
Imbalance
percent threshold at the
start of the
MPM Convergence Period
.
MPM Stable
Threshold*
Mid-point
Imbalance
percent threshold after the
convergence period.
* A dynamic alarm threshold is used to give the best possible battery fault detection:
1
After the end of a discharge, Fast Charge or Equalize cycle, MPM does not start until the
end of the
MPM Lockout Period
, to ensure the system is in float charge.
2
At this point, the battery cell voltages are expected to be widely spread, so the alarm
threshold is set high (
MPM Start Threshold
).
3
The alarm threshold is then progressively reduced over the
MPM Convergence Period
.
4
After the end of the
MPM Convergence Period
, cell imbalance is assumed to be stable, and a
fixed threshold is used (
MPM Stable Threshold
).
Battery Time Remaining
The SC200 obtains characterization data from every full battery discharge, to a specified end
voltage.
During a battery discharge, the SC200 uses this characterization data to calculate an estimated
time until the battery will reach the specified end voltage.
If a battery disconnect LVD is fitted then the end voltage will usually be the voltage at which the
LVD disconnects the battery.
Battery Time Remaining is designed for a constant power load. The accuracy of the time
remaining calculation will be reduced if the dc power system is connected to a predominantly
resistive (constant current) load.
The time remaining calculation will not be correct if a non-essential load is disconnected during
the battery discharge.
Содержание SC200
Страница 4: ......
Страница 8: ......
Страница 28: ...SC200 Handbook 20 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 88: ...SC200 Handbook 80 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 116: ...SC200 Handbook 108 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 120: ...SC200 Handbook 112 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 130: ...SC200 Handbook 122 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 134: ...SC200 Handbook 126 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...