![Eaton SC200 Скачать руководство пользователя страница 82](http://html1.mh-extra.com/html/eaton/sc200/sc200_operation-handbook_3771908082.webp)
SC200 Handbook
74
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
System States
The SC200 monitors the following system states to provide an overview of the dc power
system's operation. States displayed will depend on the dc power system model.
Name
Description
Where to find:
Fan
Indicates if any digital input with
Function
set to
"ACD Fan Fail" is active (only used in systems
with ac distribution fans).
SC200: Digitals
DCTools/Web: Digital
Inputs
Cabinet Fan
Indicates if any digital input with
Function
set to
"Cabinet Fan Fail" is active (only used in systems
with cabinet fans).
Mains Fail
Indicates if any digital input with
Function
set to
"AC Fail" is active.
MOV Fail
Indicates if any digital input with
Function
set to
"MOV Fail" is active (only used in systems with
MOV surge protection).
Load Fuse Fail
Indicates if any digital input with
Function
set to
"Load Fuse Fail" is active.
Battery Fuse Fail
Indicates if any digital input with
Function
set to
"Battery Fuse Fail" is active.
Phase Fail
Indicates if any digital input with
Function
set to
"Phase Fail" is active.
Notes:
1
See the related Alarm Descriptions on page
2
A value of
Unavailable
indicates that a System State is not configured for this dc power
system.
3
A value of
Missing
indicates that the I/O board has been disconnected or is faulty, or the
connector mapping is incorrect.
Digital Inputs
The input/output (I/O) board is fitted with a number of configurable digital inputs (DI) which
can monitor external voltage-free relay contacts or switches. See Input/Output Board on page
for details.
► To configure a digital input
1
In DCTools/Web go to
Digital Inputs
. Expand the
Digital Inputs
table.
2
Digital Input 1-6 are available for configuration.
Digital Input 7-10 (on I/O board 1) are used for system alarms.
If additional I/O boards and/or SiteSure-3G modules are connected there will be more
configurable Digital Inputs. See details in the dc power system Installation and Operation
Guide.
The last four digital inputs are the pre-assigned Digital System States (see details on page
). Do not change these settings.
3
Select a configurable Digital Input.
4
Configure the following parameters to suit the application.
To change a setting, double-click and select from drop down list or edit the text.
Содержание SC200
Страница 4: ......
Страница 8: ......
Страница 28: ...SC200 Handbook 20 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 88: ...SC200 Handbook 80 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 116: ...SC200 Handbook 108 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 120: ...SC200 Handbook 112 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 130: ...SC200 Handbook 122 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 134: ...SC200 Handbook 126 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...