Alarm Descriptions
AC Fail
All rectifiers report ac supply failure or a digital input with
Function
set to "AC Fail"
is active.
AC Phase 1/2/3 Fail
Phase 1/2/3 of the ac input, as measured by CR48-3G rectifiers, has failed,
i.e. it deviates from the
Nominal AC Voltage
by more than the
AC Phase Fail
Threshold
. Not available in systems with other rectifier models.
AC Phase 1/2/3 Voltage
Phase 1/2/3 of the ac input, as measured by CR48-3G rectifiers, deviates
from the
Nominal AC Voltage
by more than the
AC Phase Voltage Threshold
.
Not available in systems with other rectifier models.
ACD Fan Fail
The ac distribution cooling system or fan controller has failed (indicated by an active
digital input with
Function
set to "ACD Fan Fail".
Auxiliary Sensor Fail
An I/O board has an analog input with Function
User Defined
and the input is either
out of range or unavailable.
Battery Current Limit
Battery Current Limit (BCL) is active. See Battery Current Limit on page
Battery Fuse Fail
A battery fuse has blown or a battery disconnect device has operated (indicated by
an active digital input with
Function "
Battery Fuse Fail").
Battery Temperature
High
The analog input with
Function
set to "Battery Temperature" has a value above the
Battery Temperature High Threshold
.
This alarm indicates either thermal runaway of the batteries or that the batteries are
operating at a temperature that may cause reduced battery life.
Battery Temperature
Low
The analog input with
Function
set to "Battery Temperature" has a value below the
Battery Temperature Low Threshold
.
This alarm indicates a risk to the standby power system battery as lower
temperatures reduce the battery capacity.
Battery Test
The Battery Test control process is active. See Battery Test on page
Battery Test Fail
The batteries do not have the required capacity or are not fully charged. See Battery
Test on page
Cabinet Fan Fail
A cabinet fan has failed (indicated by an active digital input with
Function
set to
"Cabinet Fan Fail").
Configuration Error
One of the following is true:
The Rectifier Current Limit is set higher than the Maximum Current Limit of all
the registered rectifiers. See details on page
The OVSD Set Point is out of the range of any registered rectifiers. See details on
page
More than one digital output are mapped to the same relay on an I/O board or
SiteSure-3G Module. See details on page
An LVD contactor is in
Conflict
state. See details on page
Smart Alarm Based Disconnect
is
Enabled
, but the corresponding
Smart Alarm
is
Disabled
. See details on page
A
Smart Alarm
source has an invalid
Source Triggered
setting.
DO Manual
A digital output is set to manual control (control state is set to
Active
or
Inactive
). See
Digital Outputs on page
Equalize
The Equalize control process is active. See Equalize on page
Fast Charge
The Fast Charge control process is active. See Fast Charge on page
Содержание SC200
Страница 4: ......
Страница 8: ......
Страница 28: ...SC200 Handbook 20 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 88: ...SC200 Handbook 80 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 116: ...SC200 Handbook 108 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 120: ...SC200 Handbook 112 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 130: ...SC200 Handbook 122 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 134: ...SC200 Handbook 126 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...