5 Operation
5.4 Operational hazard warnings
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
111
NOTICE
Any contactors and switching devices on the line side are not to
be opened during motor operation. Inching operation using the
mains contactor is not permitted.
Contactors and switchgear (repair and maintenance switches)
on the motor side must not be opened while the motor is in
operation.
Inching operation of the motor with contactors and switching
devices in the output of the variable frequency drive is not
permissible.
NOTICE
Make sure that starting the motor will not put anyone or
anything in danger.
Disconnect the driven machine if there is a danger in an
incorrect operating state.
→
If motors are to be operated with frequencies higher than the
standard 50 or 60 Hz, then these operating ranges must be
approved by the motor manufacturer. The motors could be
damaged otherwise.
Содержание PowerXL
Страница 4: ......
Страница 124: ...5 Operation 5 7 Handling the keypad 120 DC1 S 20 DC1 S OE1 Variable Frequency Drives 05 21 MN040058EN www eaton com...
Страница 160: ...6 Parameter structure 6 7 Fault messages 156 DC1 S 20 DC1 S OE1 Variable Frequency Drives 05 21 MN040058EN www eaton com...
Страница 170: ...7 Technical Data 7 3 Dimensions 166 DC1 S 20 DC1 S OE1 Variable Frequency Drives 05 21 MN040058EN www eaton com...