6 Parameter structure
6.5 Messages
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
141
6.5.2 Messages after a data transfer with a DX-COM-STICK2
Table 46: Possible messages after a data transfer
6.5.3 Operating status indicators
The six flashing dots on the seven-segment display are used to indicate
various operating statuses.
4-20 F
The analog input’s input current does not fall within the specified range.
• Check the setting in P-16 for AI1 and P-47 for AI2
In the case of 4-20mA:
• Check the setpoint connection for wire breakage
SC-FLt
Internal error
• Please contact your nearest Eaton sales branch
FAVLty
Internal error
• Please contact your nearest Eaton sales branch
Message
Possible causes and fixes
View
Description
PASS-r
Parameter transfer to DX-COM-STICK2 was successful
OS-Loc
DX-COM-STICK2 locked.
In order to transfer data, check the switch position on the side.
FAiL-r
Error while attempting to read the parameters from the variable frequency drive.
PASS-t
Parameter transfer to variable frequency drive successful.
FAiL-P
The parameter set stored in the DX-COM-STICK2 is for a different rating (different motor
current, motor output, etc.) than that of the connected variable frequency drive.
Fail-t
Error when attempting to copy parameter set to variable frequency drive
no-dAt
No data found in DX-COM-STICK2.
dr-Loc
Parameter set in variable frequency drive locked. Unlock variable frequency drive first.
dr-rVn
The variable frequency drive has an enable signal and cannot take new parameters.
Stop the variable frequency drive.
tyPE-E
The parameter set stored in the DX-COM-STICK2 does not match the variable frequency drive.
Only transfers from the variable frequency drive to the DX-COM-STICK2 are possible.
tyPE-F
The DX-COM-STICK2 is not compatible with the variable frequency drive.
8 . 8 . 8 . 8 . 8 . 8 .
↓
↓
↓
↓
↓
↓
1
2
3
4
5
6
Number(s)
Behavior
Meaning
1, 2, 3, 4, 5, 6
Flash synchronously
Overload
The current current exceeds the value set with P-08.
1, 6
Flash in an alternating
pattern
Power outage or power supply switched off
1
flashes
Fire Mode enabled