6 Parameter structure
6.6 Parameter
154
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
P-49
PID1 WakeUpLevel
0.00 %
100.00 %
Wake-up level controller 1
Sets an error level (difference between the PID
reference and feedback values) above which the
PID controller will wake from Standby mode.
Sets an error level (difference between PI set point
and feedback values) above which the PI controller
will wake from standby mode.
0.00 %
P-50
CAN0 Baudrate
0
3
CANopen Baudrate
Sets the Baudrate in case CANopen is used
0: 125 kBit/s
1: 250 kBit/s
2: 500 kBit/s
3: 1000 kBit/s
2
P-51
T-Memory Enable
0
1
If this function is enabled, the computed thermal
model for the motor will be automatically saved
when the supply voltage is switched off. The
stored values will then be used when it is switched
back on. If this function is disabled, the motor
thermal history is reset to zero on every power up.
0: Thermal memory disabled
1: Thermal memory enabled
0
P-52
ParameterAccess
0
1
Parameter Access
0: All parameters can be changed by any source.
1: All parameters locked; can only be changed by
the SWD Device.
0
P-53
Action@Communication
Loss
0
4
Device reaction after occuring of “Communication
Loss”. Possibilities device dependent
Drive reaction after SWD master communication
loss. Master communication loss delay time is set
by ”Modbus RTU COM Timeout” (P-36)
0: No reaction, continue work
1: Set warning, continue work
2: stop (if ramp enabled)
3: quick stop
4: coast stop
0
P-54
RO1 Hysteresis
0.00 %
100.00 %
Hysteresis for relay output 1
This parameter defines a lower switching
threshold if P-18 is set to 4, …, 7.
Threshold level = limit (P-19) - hysteresis (P-54)
P-18 = 4 or 5: output will be logic 1 if the value
≧
limit , output will be logic 0 if value < level
P-18 = 6 or 7: output will be logic 0 if the value
≧
limit, output will be logic 1 if value < level
0.00 %
P-55
RO1 Switch-On Delay
0.0 s
250.0 s
Delay time before the Relay switches from logic 0
to logic 1.
0.0 s
P-56
Reserved Parameter
0.0 s
250.0 s
Reserved Parameter
0.0 s
P-57
Reserved Parameter
0.0 s
250.0 s
Reserved Parameter
0.0 s
P-58
Reserved Parameter
0.0 s
250.0 s
Reserved Parameter
0.0 s
P-59
Reserved Parameter
0.0 s
250.0 s
Reserved Parameter
0.0 s
Para-
meter
Designation
min. value
max. value
Description