6 Parameter structure
6.4 Control signal terminals
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
131
6.4.2.5 P-12 = 5: PI controller
Table 37: P-12 = 5: PI controller
P-15
DI1
(terminal 2)
DI2
(terminal 3)
DI3/AI2
(terminal 4)
DI4/AI1
(terminal 6)
0
START
Select PI REF/f-Fix1
PI feedback
No function
1
Select PI REF/AI1 REF
PI feedback
AI1 REF
2
Not permissible
3
START
Select PI REF/f-Fix1
EXTFLT
PI feedback
4
Not permissible
5
Not permissible
6
Not permissible
7
Not permissible
8
Not permissible
9
Not permissible
10
Not permissible
11
Not permissible
12
Not permissible
13
Not permissible
14
Not permissible
15
START
Select f-Fix4/PI REF
Select Fire Mode/Normal OP
No function
16
1)
START
Select f-Fix4/f-Fix2
Select Fire Mode/Normal OP
No function
17
1)
START
Select f-Fix2/f-Fix4
Select Fire Mode/Normal OP
No function
1) If P-15 = 16 or 17, the fixed frequencies will only be enabled in fire mode.