47
Chapter 4 - Standard
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
MN040049EN
—September 2021 www.eaton.com
Table 20. System (Cont.).
P13.2.7
Fan control
ID 632
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
2
Options:
0 = Continuous - fan runs continuously.
1 = Temperature - based on the temperature of the unit. The fan is switched on automatically when the heat sink temperature reaches
60°C (140°F). The fan receives a stop command when the heat sink temperature falls to 55°C (131°F). The fan runs for about a
minute
after receiving the stop command or switching on the power, as well as after changing the value from “Continuous” to
“Temperature”.
2 = Run follow - after power up, the fan is stopped until the run command is given and then fan runs continuously. This is mainly made
for common DC-bus systems to prevent cooling fans to load charging resistors on power up moment.
Description:
This function allows you to control the DM1 PRO’s cooling fan.
P13.4 - Version information.
P13.4.1
Keypad software version
ID 640
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Description:
Keypad firmware version.
P13.4.2
Motor control software version
ID 642
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Description:
DSP/motor control software version.
P13.4.3
Application software version
ID 644
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Description:
MCU/application software version.
P13.4.4
Software bundle version
ID 1714
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Description:
Software bundle version.
P13.5 - Application information.
P13.5.1
Serial number
ID 648
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Description:
Product serial number.
P13.5.2
Multi-monitor set (for remote keypad only)
ID 627
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Change enable; or
1 = Change disable.
Description:
The keypad display can display three actual monitored values at the same time. This parameter determines if the operator is allowed to
replace the values monitored with other values.
P13.5.3
Keypad lock PIN
ID 75
Minimum value:
0
Maximum value:
9,999
Default value:
0
Description:
The keypad can be protected against unauthorized changes with the keypad lock function after keys are not pressed five minutes.
When the password function is enabled, the user will be prompted to enter a password before the keypad display parameter or
response to key press except up/down/left/right.
By default, the password function is not in use. If you want to activate the password, change the value of this parameter to any number
between 1 and 9,999.
To deactivate the password, reset the parameter value to 0.
P13.5.4
Drive application name
ID 2922
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
a
Parameter value can only be changed after the drive has stopped.