Table 45. Protections (Cont.).
P6.3.2
ab
OPTcard fault response
ID 335
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
2
Options:
0 = No action;
1 = Warning;
2 = Fault; or
3 = Fault, coast.
Description:
This sets the response mode for a board slot fault caused by a missing or failed option board not communicating to the central
processor.
a
Parameter value can only be changed after the drive has stopped.
b
Parameter value will be set to be default when changing macros.
Table 46. PI Controller (Cont.).
P7.1 - Basic settings.
P7.1.1
b
PI contro
l gain
ID
1294
Minimum value:
0.00%
Maximum value:
200.00%
Default value:
100.00%
Description:
Defines the gain of the PI Controller. It adjust the slope of the speed increase according to the initial of the load. If this value is set to
100%, a change of 10% in the error value causes the controller output to change 10%.
P7.1.2
b
PI control itime
ID
1295
Minimum value:
0.00 s
Maximum value:
600.00 s
Default value:
1.00 s
Description:
Defines the integration time of the PI controller. Over the time, the integral time contributes to the deviation between the reference
and the feedback signal. If this value is set to 1.00 sec., a change of 10% in the error value causes the controller output to change by
10.00%/s.
.