179
Chapter 7- Multi-purpose application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
MN040049EN—September 2021 www.eaton.com
Table 59. Outputs (Cont.).
P3.2.21
b
AI supervision select
ID 170
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Analog reference from AI; or
1 = Analog reference from keypad potentiometer.
Description:
Selects analog signal to use for the analog input supervision.
P3.2.22
b
AI limit supervision
ID 171
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = No limit;
1 = Low limit supervision; or
2 = High limit supervision.
Description:
Selects analog signal to use for the analog input supervision.
P3.2.23
b
AI limit display
ID 1826
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Enable DO;
1 = Warning (W/O S)/enable DO;
2 = Warning (W S)/enable DO; or
3 = Fault/enable DO.
Description:
Supervision display selection.
P3.2.24
b
AI limit supervision value
ID 172
Minimum value:
1.00%
Maximum value:
10.00%
Default value:
0.00%
Description:
Selects the analog reference value supervised by the analog reference limit supervision function.
P3.2.25
b
AI supervision hysteresis
ID 2198
Minimum value:
1.00%
Maximum value:
10.00%
Default value:
1.00%
Description:
This value selects the bandwidth between when the AI supervision enables and disables.
P3.2.26
b
Motor current supervision
ID 2189
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = No limit;
1 = Low limit supervision; or
2 = High limit supervision.
Description:
Selects how the motor current limit supervision controller functions.
P3.2.27
b
Motor current limit display
ID 1827
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Enable DO;
1 = Warning (W/O S)/enable DO;
2 = Warning (W S)/enable DO; or
3 = Fault/enable DO.
Description:
Supervision display selection.
P3.2.28
b
Motor current supervision value
ID 2190
Minimum value:
0.00 A
Maximum value:
DriveNomCurrCT*2 A
Default value:
DriveNomCurrCT A
Description:
Selects the motor current value supervised by the motor current limit supervision function.
P3.2.29
b
Motor current supervision hysteresis
ID 2196
Minimum value:
0.10 A
Maximum value:
1.00 A
Default value:
0.10 A
Description:
This value selects the bandwidth between when the motor current supervision enables and disables.