151
Chapter 7- Multi-purpose application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
MN040049EN—September 2021 www.eaton.com
Table 55. Multi-pump status (Cont.)
.
M7.1.2
Drive 2
ID 2230
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
0 = Offline;
1 = Slave drive;
2 = Master drive; or
3 = Redundant drive.
Description:
Provides the operating mode of drive 2 while using multi-pump mode.
M7.1.3
Drive 3
ID 2242
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
0 = Offline;
1 = Slave drive;
2 = Master drive; or
3 = Redundant drive.
Description:
Provides the operating mode of drive 3 while using multi-pump mode.
M7.1.4
Drive 4
ID 2254
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
0 = Offline;
1 = Slave drive;
2 = Master drive; or
3 = Redundant drive.
Description:
Provides the operating mode of drive 4 while using multi-pump mode.
M7.1.5
Drive 5
ID 2266
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
0 = Offline;
1 = Slave drive;
2 = Master drive; or
3 = Redundant drive.
Description:
Provides the operating mode of drive 5 while using multi-pump mode.
M7.2 - Multi-pump status (*DM1 Pro).
M7.2.1
Drive 1
ID 2219
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
5
Options:
0 = Stopped;
1 = Sleep;
2 = Regulating;
3 = Wait for CMD
4 = Following; or
5 = Unknown.
Description:
Provides the run status of drive 1 while using the multi-pump mode.
M7.2.2
Drive 2
ID 2231
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
5
Options:
0 = Stopped;
1 = Sleep;
2 = Regulating;
3 = Wait for CMD
4 = Following; or
5 = Unknown.
Description:
Provides the run status of drive 2 while using the multi-pump mode.