Chapter 7- Multi-purpose application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
MN040049EN
—September 2021 www.eaton.com
Table 59. Outputs (Cont.).
P3.3.6
b
AO value minimum
ID 1867
Minimum value:
0.00 varies
Maximum value:
100.00 varies
Default value:
0.00 varies
Description:
Start point output axis y1, define AO value selected by AO mode, y1 is related to x1.
Default value is 0 mA.
From (x1,y1) and (x2,y2) will get gain and offset. Then expected AO will calculate from gain and offset.
P3.3.7
b
AO value maximum
ID 1868
Minimum value:
0.00 varies
Maximum value:
100.00 varies
Default value:
20.00 varies
Description:
End point output axis y2, define AO value selected by AO mode, y2 is related to x2.
Default value is 20 mA.
From (x1,y1) and (x2,y2) will get gain and offset. Then expected AO will calculate from gain and offset.
b
Parameter value will be set to be default when changing macros.
Table 60. Drive control (Cont.).
P4.1 - Basic settings.
P4.1.1
b
Keypad reference
ID 141
Minimum value:
MinFreq Hz
Maximum value:
MaxFreq HZ
Default value:
0.00 Hz
Description:
Keypad reference value.
P4.1.2
b
Keypad/drive reference pot direction
ID 141
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options”
0 = Forward; or
1 = Reverse.
Description:
Forward - the rotation of the motor is forward or clockwise direction, when the keypad is the active control place.
Reverse - the rotation of the motor is reversed or counter clockwise direction, when the keypad is the active control place.
P4.1.3
b
Keypad stop
ID 114
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
1
Options:
0 = Enabled - keypad operation - In this mode, the keypad stop will only operate when the control source is set to keypad.
1 = Always enabled - In this mode, the stop button will always stop the drive regardless of control mode.
Description:
Enabled or always enabled keypad operation.
P4.1.4
a
Reverse enabled
ID 1679
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
1
Options:
0 = Disabled; or
1 = Enabled.
Description:
Enables or disables the reverse motor direction.
P4.1.5
Change phase sequence motor
ID 2515
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Change disable; or
1 = Change enable.
Description:
This parameter allows for swapping the motor phase output from u, v, w to u, w, v.
P4.1.6
b
Power up local remote select
ID 1685
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Hold last;
1 = Local control; or
2 = Remote control.
Description:
Selects what control place the drive will start at after power is applied. The default setting will hold the last state that the drive was in
when powered down, selecting Local or Remote will cause the drive to start in that mode regardless of last state.
.