199
Chapter 7- Multi-purpose application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
MN040049EN—September 2021 www.eaton.com
Table 62. Protections (Cont.).
P6.2.17
ab
Overcurrent controller response
ID 1841
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = No action;
1 = Warning (W/O S); or
2 = Warning (W S).
Description:
Display options for current limit controller warning.
P6.2.18
Cold weather password
ID 2129
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Description:
This password allows access to override the under temperature fault protection. This parameter is seen by pressing the left and right
soft keys on the keypad. Password should be set to 62385. This value gets reset on cycle of power.
P6.2.19
Under-temperature fault override
ID 2130
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = No; or
1 = Yes.
Description:
With the password set to the correct value, this parameter is enabled and will give the ability to override the under temp fault. This
function gets reset when power is cycled.
P6.3 - Communications.
P6.3.1
ab
Fieldbus fault response
ID 334
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
2
Options:
0 = No action;
1 = Warning;
2 = Fault; or
3 = Fault, coast.
Description:
This sets the response mode for the fieldbus fault when a fieldbus mode is used and communication is lost between the PLC and
communication port.
Each protocol has another parameter to select in all control or only in fieldbus control to set fault or warning.
P6.3.2
ab
OPTcard fault response
ID 335
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
2
Options:
0 = No action;
1 = Warning;
2 = Fault; or
3 = Fault, coast.
Description:
This sets the response mode for a board slot fault caused by a missing or failed option board not communicating to the central
processor.
P6.3.3
ab
IP address confliction res
ponse
ID 1678
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
1
Options:
0 = No action;
1 = Warning;
2 = Fault - stop mode after fault according to parameter stop mode; or
3 = Fault - stop mode after fault always by coasting.
Description:
Indicates there is a conflict in the IP address assigned to the drive, typically meaning there are multiple devices with the same IP
address assigned. .
P6.3.4
ab
Keypad communication fault response
ID 2157
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = No action;
1 = Warning;
2 = Fault; or
3 = Fault, coast.
Description:
This parameter defines the function of the keypad communication response in the case the keypad is removed.