Chapter 4 - Standard
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
MN040049EN
—September 2021 www.eaton.com
Table 9. Parameters (Cont.).
P1.4
b
Decel. time 1
ID 104
Minimum value:
0.1 s
Maximum value:
3,000.0 s
Default value:
20.0 s
Description:
Defines the time required for the output frequency to decelerate from maximum frequency to zero frequency.
P1.6
a
Motor nom. current
ID 486
Minimum value:
DriveNomCurrCT*1/10 A
Maximum value:
DriveNomCurrCT*2 A
Default value:
DriveNomCurrCT A
Description:
Motor nameplate rated full load current. This value is found on the rating plate of the motor.
P1.7
a
Motor nom. speed
ID 489
Minimum value:
300 rpm
Maximum value:
20,000 rpm
Default value:
MotorNomSpeedMFG
Description:
Motor nameplate rated speed. This value is found on the rating plate of the motor.
P1.8
a
Motor PF
ID 490
Minimum value:
0.30
Maximum value:
1.00
Default value:
0.85
Description:
Motor nameplate rated power factor. This value is found on the rating plate of the motor.
P1.9
a
Motor nom. voltage
ID 487
Minimum value:
180 V
Maximum value:
690 V
Default value:
MotorNomVoltMFG V
Description:
Motor nameplate rated voltage. This value is found on the rating plate of the motor.
P1.10
a
Motor nom. frequency
ID 488
Minimum value:
8.00 Hz
Maximum value:
400.00 Hz
Default value:
MotorNomFreqMFG Hz
Description:
Motor nameplate rated frequency. This value is found on the rating plate of the motor.
P1.11
b
Local control place
ID 1695
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = keypad;
1 = IO terminal; or
3 = fieldbus.
Description:
Defines the signal location for the start command in local mode. I/O terminals would be from the digital hard-wired inputs or keypad for
Start/Stop buttons on the drive. Fieldbus would be a communication bus. Keypad display will indicate which mode is selected.
P1.12
ab
Local reference
ID 136
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
1
Options:
0 = AI;
1 = drive ref. pot;
4 = maximum frequency;
6 = keypad; or
7 = fieldbus ref.
Description:
Defines the signal location for the speed reference in local mode.
P1.13
b
Remote control place
ID 135
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = IO terminal;
1 = fieldbus; or
3 = keypad.
Description:
Defines the signal location for the start command in remote mode. I/O terminals would be from the digital hard-wired inputs or keypad
for Start/Stop buttons on the drive. Fieldbus would be a communication bus. Keypad display will indicate which mode is selected.
P1.14
ab
Remote reference
ID 137
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = AI;
1 = drive reference pot;
4 = maximum frequency;
6 = keypad; or
7 = fieldbus reference.
Description:
Defines the signal location for the speed reference in remote mode.
a
Parameter value can only be changed after the drive has stopped.
b
Parameter value will be set to be default when changing macros.