3 Installation
3.5 EMC installation
DC1…20… and DC1…OE1 Variable Frequency Drives
02/20 MN040059EN
www.eaton.com
73
produced in compliance with standards applicable worldwide. In the case of
devices powered with a three-phase supply (DC1-3…), this fault current
must be monitored by an AC/DC-sensitive type B residual current device
(RCD).
3.5.3 EMC screw
FS1 to FS3 DC1 variable frequency drives with an IP20 degree of protection
feature a screw on the left side that is labeled EMC.
Figure 36:
EMC screw
In the case of units with a frame size of FS4, there will be two screws
labeled EMC: one next to the main terminals and another one next to the
motor terminals.
Figure 37:
Two EMC screws on devices with a frame size of FS4