3 Installation
3.6 Electrical Installation
DC1…20… and DC1…OE1 Variable Frequency Drives
02/20 MN040059EN
www.eaton.com
99
3.6.2.6 Analog input signals
Depending on how parameters P-12 and P-15 are set, control terminals
4 (AI2) and 6 (AI1) can be connected to analog signals.
Table 14: Control signal terminal 6 (AI1)
Table 15: Control signal terminal 4 (AI2)
P-16
Signal
Description
0
0 - +10 V
Frequency reference value / Speed reference value.
Manipulated variable range from minimum (P-02) to maximum (P-01) value.
Default settings.
1
0 - +10 V
Frequency reference value/speed reference value with operating direction
change depending on the parameterization (P-35, P-39)
2
0 - 20 mA
Current signal
3
4 - 20 mA
Current signal with open-circuit monitoring (< 3 mA)
→
Shutdown with fault message.
4
4 - 20 mA
Current signal with open-circuit monitoring (< 3 mA)
→
No
shutdown if a fault is detected
Operation will continue with fixed frequency/fixed speed 1 (P-20)
5
20 - 4 mA
Inverted current signal with open-circuit monitoring (< 3 mA)
→
Shutdown with fault message
6
20 - 4 mA
Inverted current signal with open-circuit monitoring (< 3 mA)
→
No
shutdown if a fault is detected
Operation will continue with fixed frequency/fixed speed 1 (P-20)
7
+10 - 0 V
Inverted voltage signal
Analog input AI1: Resolution: 12-bit, response time: < 16 ms
P-47
Signal
Description
0
0 - +10 V
Voltage signal
1
0 - 20 mA
Current signal
2
4 - 20 mA
Current signal with open-circuit monitoring (< 3 mA)
→
Shutdown with fault message.
3
4 - 20 mA
Current signal with open-circuit monitoring (< 3 mA)
→
No
shutdown if a fault is detected
Operation will continue with fixed frequency/fixed speed 1 (P-20)
4
20 - 4 mA
Inverted current signal with open-circuit monitoring (< 3 mA)
→
Shutdown with fault message
5
20 - 4 mA
Inverted current signal with open-circuit monitoring (< 3 mA)
→
No
shutdown if a fault is detected
Operation will continue with fixed frequency/fixed speed 1 (P-20)
6
Ptc-th
Thermistor connection (
Section 3.6.3, “Thermistor connection“, page 106)
Analog input AI2: Resolution: 12-bit, response time: < 16 ms
The way control terminal 4 works (DI3 AI2) can be changed with P-15 = 4 and P-12 = 6.
→
Control terminals 7 and 9 are the common 0 V reference
potential for all analog and digital input signals.