1 DC1 device series
1.4 Rated operational data
DC1…20… and DC1…OE1 Variable Frequency Drives
02/20 MN040059EN
www.eaton.com
15
Nameplate inscription
The inscription of the nameplate has the following meaning (example):
Inscription
Meaning
DC1-344D1FB-A20CE1
Part no.:
DC1 = DC1 series variable frequency drive
3 = Three-phase mains connection / three-phase motor connection
4 = 400 V mains voltage category
4D1 = 4.1 A rated operational current (4-decimal-1, output current)
F = Integrated radio interference suppression filter
B = Integrated brake chopper
A = LED display (7-segment text display)
20 = IP20 degree of protection
C = Coated boards
E1 = Expansion, version 1
Input
Rated operational data of mains connection
Three-phase AC voltage (U
e
3~ AC),
380 - 480 V voltage, 50/60 Hz frequency, input phase current (5.6 A).
Output
Load side (motor) rated operational data:
Three-phase AC voltage (0 - U
e
), output phase current (4.1 A), output frequency
(0 - 500 Hz)
Assigned motor output:
1.5 kW with a voltage of 400 V/2 HP with a voltage of 460 V for a four-pole,
internally cooled or surface-cooled three-phase asynchronous motor (1500 rpm at
50 Hz/1800 rpm at 60 Hz)
Serial No.:
Serial number
IP20
Degree of protection of the housing: IP 20, UL (cUL) Open Type
Software
Software version (2.0)
25072016
Manufacturing date: 07-25-2016
Max amb. 50 °C
Maximum permissible ambient air temperature (50 °C)
Variable frequency drive is an electrical apparatus.
Read the manual (in this case MN040023EN) before making any electrical
connections and commissioning.
a