4 Operational
4.6 Help cards
136
DC1…20… and DC1…OE1 Variable Frequency Drives
02/20 MN040059EN
www.eaton.com
Example (adjust the motor protection function)
The following example shows how to adjust the motor protection function:
View
Explanation
Operating state Stop
Press the
OK
button and hold it down for about two
seconds.
Use the
▲
(Up) or
▼
(Down) arrow key to select
parameter P-08.
Press the
OK
button to confirm.
The rated operational current (2.3 A) for the
DC1-342D3 variable frequency drive will be displayed.
Press the
▼
(Down) arrow key four times in order to
set the appropriate rated motor current (1.9 A with
400 V).
The motor protection function will be adjusted so as to
match the motor being used
Press the
OK
button and hold it down for about two
seconds to confirm.
> 1 s
4 x
= 1.9 A
> 1 s
P-08
P
-01
P
-08
Stop
Stop
A 2
.
3
A 1
.
9